Login
02051

Class 2 - Station Class, OCP2 Series

Class 2 - Station Class, OCP2 Series
larger imageMove mouse over the image to magnify
Station Class arrestors are widely used in substation applications to protect equipment from over voltages. Surge Arrestors sacrifice themselves to protect the asset they are installed with.

SPECIFICATIONS
GENERIC TECHNICAL DATA
OCP2 Series 3-41kV UC
Rated discharge current (8/20µs) 10kA
Line discharge class according to IEC 60099-4 CLASS 2
Operating duty impulse withstand current (4/10µs) 100kA
10 second temporary overvoltage (UTOV/UC) 1.35
Long duration current impulse (2000µs) 530A
High current short circuit: (pre-failing method) (Safe non-shattering failure mode) 40kA
Energy - 2 long duration impulses 6.0KJ/kV UC
Service conditions - Ambient temperature -60°C to + 60°C
MECHANICAL STRENGTH
Cantilever 250NM
Tensile 2000NM
Torque 50NM
 
DATA SHEET
OCP2-DAH EPP 1098 EN 4-14
Cat No. Rating (kA) Voltage (kV) Stud (mm) Qty
A91131-000
10
10
55
CR0615-000
10
12
55
D67995-000
10
12
55
EE2348-000
10
36
55

You might also be interested in ...

Signup for Juice & Email Specials

TransNet Juice is a regular industry publication that delivers our latest news, products and special offers to industry members.  Our email specials are available for purchase through all good electrical wholesalers.

btn signup
 

Contact us

phn1+64 9 274 3340 (NZ)
building+64 9 274 5490
mail   sales@transnet.co.nz

mail   78 Cryers Road
         East Tamaki
         Auckland    
Facebook-977 
Follow us on Facebook