MI2992 is designed for both long-term recording and troubleshooting and supports various distribution system configurations. The new platform enables comprehensive data analysis directly on the device, including live measurements and historical data
review. Users can access trends for all recorded parameters, as well as events, transients, RVCs, inrush currents, and more. For more advanced reporting and analysis, the MPVision PC software provides local or remote data transfer, automated post-processing, and report generation. Additionally, remote access via VNC Viewer allows full control of the instrument from any computer, regardless of location.
KEY FEATURES
- Full compliance with power quality standard IEC 61000-4-30 Class A;
- High-speed measurement sampling frequency;
- Predefined tailored recorder profiles for specific customised reports (minimum recording interval 200 ms);
- User-defined recorder profiles;
- Built-in wide range power supply (85 – 500 Vac); directly powered from voltage (P-N or P-P) terminals; and Li-ion battery;
- Simultaneous capture of events, inrushes, user defined alarms, RVC’s, transients, signalling;
- NTP time synchronisation;
- Automatic firmware download;
- Remote access via VNC Viewer;
- Online scope view for voltages and currents;
- Easy to identify potential power quality problems via live measurements screen;
- Measuring of harmonic components of up to the 63rd;
- Measuring supraharmonics (2.1- 14.9 kHz);
- Power-harmonics measurements;
- Simple and powerful recorder with internal storage (eMMC card), external microSD memory card (up to 32 GB);
- Data download via USB cable, SD card, USB flash drive, Ethernet;
- Automatic report creation in accordance with standards like EN 50160, IEEE 519, Codigo de Red, Osinergimin and specific custom-tailored reports or export to .xls, .csv for use with third-party software;
- Recording intervals: 200 ms (with special profile), 1 s ... 2 h (user selectable or fixed defined inside profile);
- Two independent recording intervals (per energy/demand and other values) for a userdefined profile;
- Independent recording periods (unlimited) for predefined profiles;
- Averaging intervals: avg, min, max, avgon;
- Advanced data analysis with software MPVision;
- CAT IV 600 V / CAT III 1000 V overvoltage category;
- Direct connection to 1500 DC system by using S 2149 attenuator;
- Waveform/inrush recorder, which can be triggered on event/alarms/level; transient recorder for phase lines (voltage or current) with level or envelope trigger selection running simultaneously with the general recorder; Support for DC, 50/60 Hz, 400 Hz system frequency and VFD mode;
- 4 voltage channels with wide measurement range: up to 1000 VRMS, CAT III / 1000 V, with support for MV and HV systems; 4 current channels with support for automatic clamp recognition and range selection; Compliance with IEC 61557-12 and IEEE 1459 (combined, fundamental, nonfundamental power) and IEC 62053-21 (energy);
- 10,1’’ TFT colour touchscreen;
- Advanced communication options include USB Type-C, 10/100/1000 Mbit/s Ethernet interface, certified Wi-Fi 802.11 ac/a/b/g/n, Bluetooth 4.2/BLE;
- PC software MPVision provides an easy way to download, view and analyse measured data or print reports.