APPLICATIONS
Designed for distribution of electricity and protection of electrical equipment against short-circuits and overloads with industrial fuse links. RBK pro fuse switch disconnectors are designed for distribution of electricity and protection of electrical equipment against short-circuits and overloads with industrial fuse links. They are conforming to EN 60947-1, EN 60947-3, IEC 60947-1, IEC 60947-3 standards. They are intended for installation in low voltage distribution boards, cable and metering cabinets.
CONSTRUCTION
- Thermoplastic parts of RBK pro fuse switch disconnectors are made of fibre glass strengthened polyamide with halogen free flame retardant added and have highest possible flammability class – V0,
- RBK pro fuse switch disconnectors consist of following parts:
– three pole main base with spring-loaded contacts designed for connection of circular or sector-shaped conductors, and conductors with lug terminals or bars,
– removable cover with fuse links,
- Arc chambers with steel deionization plates over top contacts,
- Silver plated contacts providing low power loss.
MOUNTING
- On mounting plate
– RBK 000 pro, RBK 00 pro, RBK 1 pro, RBK 2 pro, RBK 3,
- DIN rail
– single: RBK 000 pro,
– double: RBK 00 pro,
- On to busbar systems:
– 60 mm RBK 000 pro-S, RBK 00 pro-S, RBK 1 pro-S, RBK 2 pro-S, installation on to busbar system with hooked clamps, placed inside fuse,
– 60 mm RBK 3-S installation on busbar system using adapter with three M10 screws,
– 100 mm (RBK 2-S, RBK 1 pro-S) installation on to busbar system with hooked clamps placed inside fuse.
OPERATING CONDITIONS
- To be installed in the room free of any dust, aggressive or explosive gases,
- Altitude up to 2000 meters above sea level,
- Outdoor – in cabinets with protection degree > IP 34,
- Ambient temperature from -25 °C to +55 °C,
- Relative humidity of the air should not be higher than 50% at temperature of +40°.
FUNCTIONALITY
- Making and breaking operations should be done with determined movement,
- Possible connection of circular or sector-shaped conductors with bare ends (V-terminals, 2V-terminals) or conductors with lug terminals (screw terminals),
- Voltage test performed through test holes in fuse link cover,
- Fuse links state monitoring.
TECHNICAL SPECIFICATIONS
Parameter |
|
RBK 000 pro |
RBK 00 pro |
RBK 1 pro |
RBK 2 pro |
RBK 3 pro |
Rated Thermal Current Ith1) |
A |
160 |
400 |
250 |
400 |
630 |
Rated Voltage Un |
V |
690 |
690 |
690 |
690 |
690 |
Utilisation Category |
- |
AC-23B |
AC-22B |
AC-22B |
AC-21B |
DC-21B |
AC-23B |
DC-22B |
DC-21B |
AC-23B |
DC-22B |
AC-23B |
DC-22B |
DC-21B |
AC-23B |
AC-22B |
DC-21B |
Rated Switching Current Ie |
A |
100 |
100 |
160 |
160 |
160 |
160 |
160 |
160 |
250 |
250 |
400 |
400 |
400 |
630 |
630 |
630 |
Rated Switching Voltage Ue |
V |
400 |
690 |
400 |
690 |
250 |
690 |
250 |
440 |
690 |
250 |
690 |
220 |
440 |
400 |
690 |
440 |
Rated Short Circuit Withstand Current |
690 V |
kA |
25 |
25 / 250V |
80 |
25 / 250V |
80 |
25 / 250V |
80 |
25 / 250V, 15 / 440V |
80 |
35 / 440V |
500 V |
80 |
- |
- |
- |
- |
400 V |
- |
100 |
100 |
100 |
- |
Rated Short Circuit Making Current |
690 V |
kA |
25 |
25 / 250V |
80 |
25 / 250V |
80 |
25 / 250V |
80 |
25 / 250V, 15 / 440V |
80 |
35 / 440V |
500 V |
80 |
- |
- |
- |
- |
400 V |
- |
100 |
100 |
100 |
- |
Rated Insulation Voltage Ui |
V |
1000 |
1000 |
1000 |
1000 |
1000 |
Rated Impulse Withstand Voltage Uimp. |
kV |
8 |
8 |
8 |
12 |
12 |
Rated Frequency |
Hz |
50-60 |
- |
50-60 |
- |
50-60 |
- |
50-60 |
- |
50-60 |
- |
Mechanical Durability |
|
2000 |
1600 |
1600 |
1600 |
1000 |
1000 |
Electrical Durability |
300 |
200 |
200 |
200 |
200 |
200 |
IP Degree of Protection |
IP |
20 |
20 |
20 |
20 |
20* |
Weight |
kg |
~0.6 - ~0.9 |
~0.7 |
~2 |
~3 - ~4.5 |
~4.3 |
Fuse Link Size |
- |
000 |
0 |
1 |
2 |
3 |