Industrial-grade VPFR Series (Viewing Pane Fixed Reinforced) infrared (IR) windows enable thermographers to survey critical electrical applications efficiently and safer than ever.
NFPA standards recommend IR inspection under fully energized conditions. However, PPE requirements, panel cover removal and re-installation are time consuming and costly. Use of the VPFR Series IR windows nearly eliminates the risks associated with energized IR electrical inspection by providing companies with a non-invasive, closed-panel inspection methodology.
Thermographers using IR windows are never exposed to energized conductors or circuit parts and are not engaged in risk increasing behaviours. Therefore, elevated levels of PPE for invasive surveys are not required, minimizing survey time while maximizing safety.
Protected by the IRISS unconditional lifetime warranty.
SPECIFICATIONS
MATERIALS |
Window Housing and Cover |
UL 94 5VA Nylon (switchgear-grade plastic); -40°C (-40°F) to 273°C (523°F); Easy-Grip™ stainless steel cover |
Optic |
UL 746 compliant, IR transmissive polymer; -40°C (-40°F) to 325°C (617°F) |
Reinforcing Grill |
Aluminium coated with UL 94 5VA Nylon; -40°C (-40°F) to 273°C (523°F) |
Gaskets |
UL 94 5VA TPE; -40°C (-40°F) to 273°C (523°F) |
Hardware |
316 Stainless Steel |
|
OTHER |
Useful Temperature Rating |
-40°C (-40°F) to 200°C (392°F) |
Water and Dust Ingress |
IP65 / NEMA 4: closed and when in use |
FEATURES
- Fixed And Stable Transmission (FAST)
- Unconditionally guaranteed against transmission loss for accurate qualitative and quantitative analysis
- Durable, fully impact-resistant
- Patented reinforced grill exceeds high voltage switchgear viewing pane standards
- Manufactured from non-conductive UL 94 plastics insulated to 30kV/mm
- Easy-Grip™ stainless steel cover
- Fitting templates and instructions included
- Reinforcing grills comply with IP2x standard for safe maximum hole size and fail-safe design
CERTIFICATIONS
- Certified by UL (USA) & cUL (Canada) to the following standards:
- 50V
- 50E
- 746C: Impact and Flammability
- 1558: Impact and Load Resistance
- 508A; ANSI 508A
- IEEE C37 20.2.a.3.6: Impact and Load
- IP65 / NEMA 4
- Lloyds of London Type Approval
- American Bureau of Shipping (ABS)
- BSI Quality ISO 9001 Certified System
- CSA C22.2 No. 14-13
- DNV (Det Norske Veritas) P261.1E Maritime, Vessel and Offshore Applications
DIMENSIONS
MODEL |
BODY DIAMETER |
WINDOW DIAMETER |
ASSEMBLY THICKNESS |
VPFR-50 |
9.1 cm (3.6 in) |
5.1 cm (2.0 in) |
2.6 cm (1.0 in) |
VPFR-75 |
12.1 cm (4.8 in) |
7.6 cm (3.0 in) |
2.6 cm (1.0 in) |
VPFR-100 |
15.1 cm (5.95 in) |
10.2 cm (4.0 in) |
2.6 cm (1.0 in) |
NOTE: The dimensions listed above are not installation dimensions. Do NOT cut prior to receiving your IRISS window and installation template.
DATASHEET