Providing electronic three phase over-current protection for systems rated through 38kV, 800A continuous current, 12.5kA symmetrical interrupting.
FEATURES
- Reliable performance, vacuum fault interrupters (for -S, -ST, -SP & LT models)
- Control flexibility including SEL-351 series, SEL-651R, GE controls and more
- Operator safety with mechanical block on trip and lockout handle
- Maintenance free operation
- Overhead, substation and dead-front pad-mount designs
- "L", "C" and "Z" style options available
- Ease of installation
- Three internal current transformers
- Up to six internal voltage sensors
- Smart Grid solutions
- RUS accepted
- Painted Stainless Steel tank
- Designed, built and tested to IEEE C37.60 and IEC 62271-111 standards latest version.
OPERATION OPTIONS
- DEAD LINE –Permits using batteries located in the control for operation when main control power is lost
- CUSTOM RELAY SOLUTIONS (CRS) – Permits using 48V DC or 125V DC control logic voltage as an alternative to traditional 14-pin SEL, Cooper & GE controls. Recloser power is not affected.
- INTERNAL VOLTAGE SENSING – Permits voltage reading for network reconfiguration applications and provides secondary analogue 120V AC output.
- MANUAL OPERATION – Hookstick operable manual trip handle trips and locks out the recloser
For build options and site-ready designs, please contact TransNet.
VIPER S/ST OPTIONS
OPTIONS AVAILABLE FOR THE VIPER–S/ST RANGE
- Solid Dielectric voltage transformers – Single or Three Phase
- External current transformers
- Seismic rated substation stand available includes 45° mounting
- Stainless Steel mounting frames
- Enclosures for Pad-mount models
- Auxiliary contacts
- Side mount "Alley" Pole mount
- Models with 6 Integral Capacitive Voltage Sensors are now available (suffix -6VS)
- SEL-651R2 relay can be packaged with the -6VS models if required
TECHNICAL SPECIFICATIONS
VOLTAGE CLASS (kV) |
15 |
25 |
35 |
MAX SYSTEM VOLTAGE (kV) |
15.5 |
27 |
38 |
BIL (kV) |
110 |
125 |
150 |
CONTINUOUS CURRENT (A) |
800 |
8HR. OVERLOAD AT 20°C |
960 |
60Hz WITHSTAND, kV RMS DRY, 1 MIN |
50 |
60 |
70 |
60Hz WITHSTAND, kV RMS WET, 10 SEC |
45 |
50 |
60 |
INTERRUPTING RATING RMS (kA) |
12.5 |
MAKING CURRENT, RMS, ASYM, kA |
20 |
PEAK, ASYM (kA) |
32 |
SHORT CIRCUIT CURRENT, kA SYM, 3 SEC |
12.5 |
MECHANICAL OPERATIONS |
10K |
TEMPERATURE RANGE |
-40°C TO 65°C |
DATASHEETS